General Tools
intrysys.com
Provides electrical code calculations for wire sizing, voltage drop, conduit fill, and box fill.
ENDPOINT 1
https://www.intrysys.com/api/mcp
MCP server metadata
- Name
- intry
- Version
- 1.0.0
Free, code-accurate field calculators for the trades (HVAC + electrical). Every result carries a structured readout and the cited NEC 2023 section, manufacturer data, industry standard, federal rule, or bend geometry it was computed from, plus a verdict where the reading calls for one. Each tool answers one reading completely; the Intry app keeps a whole job's readings as one job, and one tap ships it to the user's AI for the sequenced next steps: https://www.intrysys.com/app?ref=mcp
Known tools 18
voltage_dropCompute voltage drop for a copper or aluminum branch/feeder run using the NEC K-factor method (VD = 2·K·I·L / CM, K=12.9 Cu / 21.2 Al).
Potential side effectswire_sizeSize a conductor for a load per NEC 310.16 with temperature correction (310.15(B)(1)), conduit-fill bundling (310.15(C)(1)), the 110.14(C) terminal cap, the 240.4(D) small-conductor limit, and the matching EGC (250.122).
Potential side effectsev_chargerSize a Level 2 EV charger circuit per NEC Article 625: conductor and breaker at 125% continuous, EGC, GFCI requirement, receptacle vs hardwire, and a rule-of-thumb panel-capacity check.
Inferred read-onlyconduit_fillCheck conduit fill compliance per NEC Chapter 9 (53% one wire, 31% two, 40% three or more; 60% for a nipple ≤24").
Inferred read-onlybox_fillCompute junction/device box fill per NEC 314.16: conductor volume allowances, the device yoke (2×), clamps (1×), grounds (1×), and support fittings.
Inferred read-onlysuperheat_subcoolingDiagnose refrigerant charge from gauge readings: superheat = suction line temp minus saturation temp at suction pressure; subcooling = saturation temp at liquid pressure minus liquid line temp.
Potential side effectsmca_mocpFrom an HVAC nameplate MCA and MOCP (or from compressor RLA + fan FLA in RLA mode), return the minimum wire size (NEC 310.16, copper and aluminum), the breaker (largest standard 240.6(A) rating not exceeding MOCP per 440.22), the ground (250.122), and voltage drop.
Potential side effectsline_setSize the liquid and suction line set for R-454B, R-32, or R-410A by tonnage and length, and return a REUSE / FLUSH & REUSE / REPLACE verdict for an existing R-410A (or R-22) set, with the per-foot charge adjustment.
Potential side effectsload_can_panel_handleAnswer 'can my existing panel handle a new load (EV charger, heat pump, ...)?' using the NEC 220.87 existing-dwelling method: 125% of the measured 12-month peak demand plus the new load, compared to the service rating.
Inferred read-onlyconduit_offsetMarks and shrink for an EMT offset bend: distance between bends = offset depth × multiplier (1/sin θ: 10°=6, 22.5°=2.6, 30°=2, 45°=1.4, 60°=1.2), plus the run shrink.
Inferred read-onlywater_heater_circuitSize the branch circuit for an electric or heat-pump (hybrid) water heater per NEC 422.13 (a fixed storage water heater 120 gal or less is a continuous load, sized at 125%): conductor (310.16), breaker (240.6(A) with the 240.4(D) small-conductor limit), and EGC (250.122).
Inferred read-onlyinduction_range_circuitSize the branch circuit for a 120V plug-in (battery-buffered) induction range or cooktop from its WALL / CHARGE draw (NEVER the 5-10 kW induction burner peaks, which are battery-fed): conductor (310.16), breaker (240.6(A) with the 240.4(D) small-conductor limit), and EGC (250.122), given both non-continuous and continuous (>=3h recharge, 125% per 210.20(A)) branches.
Potential side effectsmax_ev_chargerAnswer 'what is the BIGGEST EV charger I can install without a panel upgrade?' Inverts the NEC 220.87 existing-load method: from the service size and the measured 12-month peak demand it returns the largest standard EVSE output that fits (the added charger enters the 220.87 service check at 100% of its 220.57 value, so headroom / voltage, floored to a standard rating; the 125% continuous factor sizes only its branch) plus the branch wire/breaker/ground.
Inferred read-onlysolar_backfeed_breakerAnswer 'how big a solar/PV backfeed breaker can this panel take?' using the NEC 705.12(B)(2) 120% rule for a busbar supplied from opposite ends: the backfeed breaker is capped at 120% of the busbar ampacity minus the main breaker, rounded DOWN to a standard 240.6(A) size (a raw 55 A allowance is not a real breaker, so it becomes 50 A).
Inferred read-onlycold_climate_hp_capacityFor a specific cold-climate heat pump model, return its MAX heating capacity at any outdoor temperature (linear interpolation of the printed 47/17/5F rated points, clamped at the lowest rated row, never extrapolated colder), the maintained-% at 5F against BOTH denominators (MAX@5 / rated@47 and MAX@5 / MAX@47, each with its source BTU numbers), the COP at MAX at 5F, and, when a design heat load and design outdoor temperature are supplied, the balance point and backup heat as a READOUT.
Inferred read-onlya2l_charge_limitThe maximum A2L refrigerant charge (R-454B, R-32, and 6 more) for a room, or the minimum room area for a given charge, per UL 60335-2-40 4th ed Annex GG and ASHRAE 15.2-2022.
Potential side effectsoutdoor_hvac_gfciDecide whether an outdoor outlet at a DWELLING needs GFCI protection under NEC 210.8(F), keyed to the jurisdiction's own amendments.
Inferred read-onlyCONNECT WITH APPROVAL
Client installation
Review this server and its permissions before adding it. Secret placeholders must be set locally.
Codex
~/.codex/config.toml
[mcp_servers.intry]
url = "https://www.intrysys.com/api/mcp"
enabled = true
Claude Code
.mcp.json
{
"mcpServers": {
"intry": {
"type": "http",
"url": "https://www.intrysys.com/api/mcp"
}
}
}
Claude Desktop
Settings → Connectors → Add custom connector
Name: intry
Remote MCP URL: https://www.intrysys.com/api/mcp
Add this remote URL as a custom connector in Claude Desktop. Availability depends on the user plan and workspace policy.
Cursor
.cursor/mcp.json
{
"mcpServers": {
"intry": {
"url": "https://www.intrysys.com/api/mcp"
}
}
}
Visual Studio Code
.vscode/mcp.json
Add to Visual Studio Code{
"servers": {
"intry": {
"type": "http",
"url": "https://www.intrysys.com/api/mcp"
}
}
}
Generic MCP
Client-specific MCP configuration
{
"name": "intry",
"transport": "streamable-http",
"url": "https://www.intrysys.com/api/mcp"
}
MCP Inspector
Run the official MCP Inspector locally and enter the indexed Streamable HTTP endpoint.
TRUST AND VERIFICATION EVIDENCE
Trust Data Available
BuiltWith Trust API v2 evidence for intrysys.com was fetched 2026-08-23T20:58:33.772Z.
intrysys.com is assessed as Neutral: No suspicious signals found, but no strong positive signal either
Evidence is source-attributed and does not guarantee that a third-party server is safe. Risk labels are conservative metadata heuristics.